Capacitor Voltage Transformer (CVT)
36~765kV Capacitor Voltage Transformer are installed on 36~765kV earthed neutral electrical systems whose rated frequency is 50Hz or 60Hz to meter Voltage energy and provide relay protection signal. Additionally, Capacitor Voltage Transformer serves as a coupling capacitor. Voltage Transformer consists of two assemblies: the capacitor sections and the electromagnetic components; It doesn’t subject to Ferro resonance oscillations with the network. At the same time, it has capability to control its own Ferro resonance oscillations; the capacitor has a small value of tanδ and temperature coefficient.
Standards
Voltage transformers are designed in accordance with IEC, DIN, ANSI, BS or other agreed standards.
Main technical parameters
Highest voltage for equipment: 36~765kV
Power frequency: 50 or 60 Hz
Rated secondary voltage:100/√3V, 110/√3V
Rated secondary voltage for the earthing core:100/3 V, 110/3 V or 100 V, 110V
Output of the metering class:100VA/0.2 ,150 VA /0,5
Output of the protection class:300VA/3P, 6P
Residual windings output:3P, 6P output: 200 VA
Ambient temperature: -40℃ to +40℃
Creepage distance: 25mm or 31mm/kV
Partial discharge level: <10pC
Main Parameter
Type |
Highest system voltage |
power
frequency
withstand
voltage |
lighting
impulse
test
voltage |
Capacitive
divider
capacitance |
kV (r.m.s) |
kV(r.m.s) |
kV (peak) |
μF |
TYD-36 |
36 |
70 |
170 |
20000 or 10000 |
TYD-72.5 |
72.5 |
140 |
325 |
20000 or 10000 |
TYD-123 |
123 |
230 |
550 |
20000 or 10000, 7000 |
TYD-145 |
145 |
275 |
650 |
20000 or 10000, 7000 |
TYD-170 |
170 |
325 |
750 |
10000 or 7000,5000 |
TYD-245 |
245 |
395 |
950 |
10000 or 7000, 5000 |
TYD-362 |
362 |
510 |
1175 |
5000 |
TYD-420 |
420 |
680 |
1550 |
5000 |
TYD-550 |
550 |
740 |
1675 |
5000 |
Indicatives values only- All indicated dimensions must be confirmed with order. |