12kV~36kV Oil Filled Instrument Transformers (Outdoor type)

12kV~36kV Oil Filled Instrument Transformers (Outdoor type)

A A A    
12kV~36kV Oil Filled Instrument Transformers  (Outdoor  type)

Catalogues:   (Download   ) 
Oil CT VT PT 12~36kV   .pdf  1.56M


12kV, 15kV 17.5kV, 24kV, 36kV Oil insulated type,  Outdoor CT, PT, VT

» Single phase, Oil-paper insulated MV current transformer   LB-, LVB series
36kV 24kV 17.5kV 15kV 12kV 7.2kV 3.6kV Current transformer,  CT

» Single phase single-pole, oil-paper insulated, inductive voltage transformer JDX-series
36kV 24kV 17.5kV 15kV 12kV 7.2kV 3.6kV Voltage transformer,  VT

» Single phase double-pole, oil-paper insulated, inductive voltage transformer JD-series 
36kV 24kV 17.5kV 15kV 12kV 7.2kV 3.6kV Voltage transformer,  VT


» Single phase, oil-paper insulated, combined voltage current transformer CVCT, JLD-series 
36kV 24kV 17.5kV 15kV 12kV 7.2kV 3.6kV Combined voltage current transformer,  CVCT


» Three phase, oil-paper insulated, Metering unit, JLSW-series 
36kV 24kV 17.5kV 15kV 12kV 7.2kV 3.6kV Metering unit



Oil-paper insulated MV current transformer   LB-,  LVB series
The current transformer of type LB-, LVB-) series is oil insulated and outdoor product. It is used for metering electric energy, current and relay, current and relay protection in electric system up to rated frequency 50Hz or 60Hz and rated voltage up-to 36kV.

          Technical specification

Type

LB-,     LVB-

Highest voltage for equipment -Um

kV

24

36

Power frequency test voltage1 min.

kV

50

70

Lighting impulse test voltageBIL

kV

125

170

Rated primary current up to

A

3000

3000

Rated secondary current

A

1 or 5

1 or 5

Rated short time thermal current -Ith

kA

Max. 50kA

Max. 63kA

Rated peak current -Idyn

kA

Max. 100kA

Max. 100kA

Burden /classes

VAcl

5-50VA/0.2, 0.3, 0.5, 1, 5P,10P

Accuracy classes

0.2, 0.3, 0.5, 1, 3, 5P,10P, PR, PX

Power frequency

Hz

50 or 60

Ambient temperature

-50℃ to +40℃

IEC standards

IEC 61869-2, IEC 60044-1

Other electrical standards

IEEE/ANSI C57.13, CAS, AS


Single-pole insulated voltage transformer   JDX-series
· The JDX series single-pole insulated voltage transformer is single phase andoil-paper insulated, inductive voltage transformer. It is used for metering electric energyvoltage control and relay protection in the electric system.

Double-pole insulated voltage transformer   JD-series
· The JD - series double-pole insulated voltage transformer is single phase andoil-paper insulated, inductive voltage transformer. It is used for metering electric energyvoltage control and relay protection in the electric system.

    Technical parameter

<td width="214" valign="top" style="border-width: medium 1pt 1pt; border-style: none solid solid; border-color: rgb(235, 233, 2 <tr style="height: 13.3pt;"

Type:                  Single-pole   JDX--

Double-pole  JD--

JDX-24

JD-24

capacitor voltage transformer


Contact us
If you are interested in our products, please contact with us by e-mail.
We will offer you detailed information for the products, such as outline dimensional drawing, technical specification, Installation and maintenance manual and etc in PDF format.

Mail: sales@sandian-electric.com,chinactvt@vip.163.com

Whatsapp: 008613974170119,   008613874108383


capacitor voltage transformer | Sitemap | Products | About us | Download | Technical | Contact us
Contact us by phone at 0086-731-23813076 or by email:chinactvt@vip.163.com
Copyright@sandian-electric 2010.Allright reseved.