72.5kV~245 kV Inductive Voltage Transformer
A A A    

36245 kV Inductive Voltage Transformer

JDCF, JDX—series voltage transformer, outdoor, oil-immersed inductive type, single phase, hermetically sealed, earthed, cascade-type voltage transformer with high accuracy and protective class secondary windings. Used for metering and relay protection, applying to highland area.

The voltage transformer consists of internal insulation parts, a porcelain insulator, oil, base, metallic bellows. The high-voltage windings are separated into two (or four) parts that are located on two poles of the core. The secondary windings are located in the lower pole of the down core. Three secondary windings are: metering, protective and residual windings. The core is designed to have low flux density. There is an oil drain plug in the base. A set of oil draining device is supplied for three transformers.

Main Technical Parameter
Highest voltage for equipment: 36--245kV
Power frequency: 50 or 60 Hz
Rated secondary voltage100/√3V, 110/√3V
Rated secondary voltage for the earthing core: 100/3 V, 110/3 V or 100 V, 110V
Output of the metering class100VA/0.2 150 VA /0,5
Output of the protection class300VA/3P, 6P
Residual windings output3P, 6P output: 300 VA
Ambient temperature: -40 to +40
Creepage distance: 25mm or 31mm/Kv
Partial discharge level: <10pC

Rated Insulated Level

Type

Highest system

Voltage

kV (r.m.s)

Power frequency

withstand voltage

kV (r.m.s)

lighting impulse

test voltage

kV (peak)

JDX-72.5

72.5

140

325

JDX -123

123

230

550

JDX -145

145

275

650

JDX -170

170

325

750

JDX -245

245

395

950

 