Station Sevrice Voltage Transformers,SSVT / Power Voltage Transformers, PVT / Oil-paper insulation type
Keywords:
SANDIAN ELECTRIC
- 产品描述
-
- Commodity name: Station Sevrice Voltage Transformers,SSVT / Power Voltage Transformers, PVT / Oil-paper insulation type
Voltage transformerare designed in accordance with IEC61869-3, ANSI/IEEE C57.13, CAN/CSA C60044-2.
Standards
Voltage transformerare designed in accordance with IEC61869-3, ANSI/IEEE C57.13, CAN/CSA C60044-2.
Power transformer are desinged in accordance with IEC 60076, ANSI/IEEE C57.12
IEEE IEC P63253-5713-8 Station service voltage transformers
Description
The SSVT is a voltage transformerinsulated in oilthat combines the characteristics of a voltagetransformer with power transformation capability.The SSVT has been designed for voltage up to 362kV and with powercapability up to 333kVA. SSVT converts the optimum power directly from high voltage side to medium/low voltage side.
The SSVT feature rugged transformer designs incorporating high creepage porcelain insulators and high over-voltage capability with impedance protection to limit fault currents. The SSVT is a line-to-ground connected single-phase transformer that can be used either as an individual unit for supplying single-phase loads, or in a three-phase bank to support larger kVA three-phase loads.
Main Technical Characteristics
• Highest system voltage: 72.5~362kV
• Rated frequency: 50Hz or 60 Hz
• Output voltage: 115V, 120V, 220V, 380V,400V,10kV, 13.8kVor according to the requirements of the clients.
• Rated power: 10, 15, 25, 50, 75, 100, 125, 150, 167, 200and 333 kVA or according to the requirements of the clients
• Partial discharge level: <10pC
• Metering accuracy class IEC: 0.2, 0.5, 1.0(If need)
• Metering accuracy class IEEE: 0.3, 0.6, 1.2(If need)
• Protection accuracy class: 3P, 6P
• Rated voltage factor: 1.2 continue, 1.5/30s
• Insulation class: E
• Temperature rise limit: ≤60K
• Ambient temperature: -50℃ to +50℃
• Creepage distance: 25mm or 31mm/Kv
• Earthquake standard design: up to 0.5g
Basic insulationlevel
Type
Highest systemVoltage
kV (r.m.s)Power frequencywithstand voltagekV (r.m.s)
lighting impulsetest voltage
kV (peak)SSVT-36
36
70
170
SSVT-72.5
72.5
140
350
SSVT-110
123
230
550
SSVT-145
145
275
650
SSVT-170
170
325
750
SSVT-245
245
460
1050
SSVT-362
362
510
1175/1300
Outline Drawing & Dimensions

Type
A(mm)
B(mm)
C(mm)
D(mm)
E(mm)
F(mm)
G(mm)
Creepage Distance
(mm)Oil Weight (l)
Total Weight (kg)
SSVT-72.5
2280
1915
760
960
935
760
650
2248
250
1100
SSVT-110
2660
2355
1150
1190
990
920
700
3813
300
1200
SSVT-145
2775
2470
1300
1190
990
920
700
4495
350
1350
SSVT-170
3625
3140
1630
1300
1180
1175
950
5270
400
1600
SSVT-245
4530
4045
1900
1550
1450
1250
1150
7595
2150
4500
345(330)kV 230kV 220kV 161kV 150kV 138kV 132kV 115kV 110kV 69kV 66kV 63kV 52kV46kV 36kV34.5kV station servicevoltage transformerSSVT.

SANDINA 138kV 220kV 345kV SSVT

SSVT-245 testing in SANDIAN.

SANDINA 220kV SSVT, Power burden: 100 kVA Type: SSVT-245, Supplied to Elecnor of Chile.

SANDINA 220kV SSVT, Power burden: 100 kVA, Operating at substation of Chile.