Inductive Voltage Transformer(IVT) / Potential Transformer(PT) / Inductive, oil paper insulation type, 24kV~550kV JDX- series, voltage transformer, potential transformer, IVT, PT
Classification :
Keywords:
SANDIAN ELECTRIC
- 产品描述
-
- Commodity name: Inductive Voltage Transformer(IVT) / Potential Transformer(PT) / Inductive, oil paper insulation type, 24kV~550kV JDX- series, voltage transformer, potential transformer, IVT, PT
Oil ImmersedPotentialTransformer(Inductive Voltage Transformer)shall be suitable for measurement control and relay protection in the outdoor AC power system of nominal voltage 36~500kV, and frequency of 50 or 60Hz.
Oil Immersed Potential Transformer(Inductive Voltage Transformer) shall be suitable for measurement control and relay protection in the outdoor AC power system of nominal voltage 36~500kV, and frequency of 50 or 60Hz.
Inductive instrument transformer of JDX- series shall be suitable for measurement control and relay protection in the outdoor AC power system of nominal voltage 36~550kV, and frequency of 50 or 60Hz, this type voltage transformers are oil immersed electromagnetic voltage transformer. The core was used cold-rolled silicon steel strip to folded single-column and three pairs of the same potential with the ground. High voltage coil main insulation chose sheet paper, small oil clearance and large structures. It was wounded as pagoda-shaped segments. High-voltage leads were insulated by a condenser bushing. We select corrugated metal expander as oil temperature variation compensator and can inspect the oil level through window. Fuel tank and the lower tank welded together, and all the other seals are made of sealed limit, effectively preventing the leakage of oil.
Main Technical Parameter
• Standards: IEC61869-3, ANSI(IEEE)C57.13, AS,BS,IS and etc
• Highest voltage for equipment: 36~550kV
• Power frequency: 50 or 60 Hz
• Rated secondary voltage: 100V, 110V, 115V, 120V, 100/3V, 110/3V,100/√3V, 110/√3V, 115/√3V
• Output of the metering class:
IEC: 5~400VA cl0.2, 0.5,1
IEEE: 0.15, 0.3, 0.6M, W, X, Y, Z, ZZ
• Output of the protection class: 5~400VA/3P, 6P
• Ambient temperature: -50℃ to +50℃
• Creepage distance: 25mm or 31mm/kV
• Partial discharge level:
1.2Um < 10pC
1.2Um√3 < 5pC
• Altitude: Standard design is less than 2000m Or higher values on request.
• Temperature rise limit: ≤60K.
• Creepage distance ratio: 25 or 31(mm/kV)
• Earthquake standard design: up to 0.5g
500kV 400kV 345(330)kV 275kV 230(220)kV 161kV 150kV 138kV 132kV 115kV 110kV 69kV 66kV 63kV 52kV 46kV 36kV 34.5kV 24kV High voltage oil immersed voltage transformer, potential voltage, PT(IVT)